Data sets for the 3RA64/3RA65 compact starter with IO-Link
A.7 Target configuration - data set (index) 130
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
305
A.7
Target configuration - data set (index) 130
WARNING
Danger of uncontrolled motor start-up
Uncontrolled motor start-up can result in injury to personnel.
The preset configuration of a compact starter group is saved by the compact starter
connected to the IO-Link master via the removable terminal.
When this compact starter is replaced, you must ensure that the preset configuration is
saved in the new compact starter. In the event of a replacement, the preset configuration
can either be transferred to the new device with the "Port Configuration Tool", or it can be
copied from the old compact starter to the new compact starter with the help of the function
block "IO-Link Call".
Note
The "compact starter" is referred to as "starter" in the table below.
Data set (index) 130 (preset configuration)
Table A- 16 Data set (index) 130 (preset configuration) - diagnostics of the starter group
Data set
Byte.Bit
Designation
Index
130
0.0...0.7
Fixed value 0x21
130
1.0...1.7
Fixed value 0x00
130
2.0...2.7
Fixed value 0x00
130
3.0...3.7
Fixed value 0x00
Diagnosis of the starter group
130
4.0...4.6
Fixed value 0x05
130
8.0...8.7
Fixed value 0x07