3RA64/3RA65 compact starter with IO-Link
6.2 Description of the hardware
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
95
6.2.3
3RA65 compact starter with IO-Link (reversing starter)
Features
The 3RA65 compact starter (reversing starter) with IO-Link is made up of the following
components:
●
Reversing starter
●
Two removable main circuit terminals
●
Two 6-pole control circuit terminals (Type A/B)
(Terminal A: L+, C/Q, L-, A2-, A1+/Y1, Y2
Terminal B: Y3, Y4)
●
Two slots for optional external auxiliary switch blocks (2 NO contacts, 2 NC contacts or
1 NO c 1 NC contact)
Control takes place via IO-Link.
Direction of rotation interlock
The operating mechanisms for the reversing starter's directions of rotation are interlocked.
This precaution prevents the operating mechanisms for direction of rotation 1 and direction
of rotation 2 from being activated simultaneously, which would result in a short circuit.
Operating mechanism interlocking is implemented on both a mechanical level (against shock
loads) and an electrical level (against incorrect activation).
Note
If direction of rotation 1 and direction of rotation 2 are triggered simultaneously, the compact
starter signals a group error and switches off.