Characteristic curves
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
291
Overview of response values
Table 12- 1 Response settings of the tripping functions
Device version I
e
Inverse-time delayed
overload release
1)
Short-time delayed
overcurrent release
Instantaneous short-
circuit release
0.4 A
0.11 - 0.45 A
1.2 - 4.8 A
56 A
1.25 A
0.36 - 1.41 A
3.8 - 15 A
56 A
4 A
1.13 - 4.5 A
12 - 48 A
56 A
12 A
3.38 - 13.5 A
36 - 144 A
168 A
32 A
9 - 36 A
96 - 384 A
448 A
1)
The specification refers to the ideal response threshold of 1.125 x I
e
(normative tripping window
between 1.05 and 1.2 x I
e
)
Displays and messages
Tripping of the inverse-time delayed overload release and the short-time delayed overcurrent
release is shown by the displays and messages in the table below.
Table 12- 2 Overload release (displays and messages)
3RA61/3RA62
3RA64/3RA65
(Device version with IO-Link)
•
The mechanical "overload release" display
(TRIP ) is white.
•
The "Group error" LED is red.
•
The signaling contact "Overload" indicates
overload (contact 95/96 is open and contact
95/98 is closed).
•
The message "overload tripped" is signaled to
the controller via IO-Link.
Short-circuit release is signaled by the displays and messages in the following table.
Table 12- 3 Short-circuit release (displays and messages)
3RA61/3RA62
3RA64/3RA65
(Device version with IO-Link)
•
The handle is in the TRIPPED position and
•
The handle is in the TRIPPED position and
•
The "Fault" signaling contact 95/96 is open.
•
The "Group error" LED is red and
•
The message "circuit breaker tripped" is
signaled to the controller via IO-Link.
You will find further information on the displays and messages in the following chapters:
●
"Diagnostics (Page 85)" for 3RA61/3RA62 compact starters
●
"Diagnostics (Page 118)" for 3RA64/3RA65 compact starters