3RA64/3RA65 compact starter with IO-Link
6.5 Process image
SIRIUS 3RA6 compact starter
112
System Manual, 09/2014, NEB560060102000/RS-AA/006
Process image output (PIQ)
The process output image contains the control commands for all compact starters.
Table 6- 8
Write process data - Control commands for the compact starter
Starter
DO (2 bytes)
Meaning
1
DO0.0
1: Motor direction of rotation 1
DO0.1
1: Motor direction of rotation 2
1)
DO0.2
1: Reserved
DO0.3
1: Trip reset
2)
2
DO0.4
1: Motor direction of rotation 1
DO0.5
1: Motor direction of rotation 2
1)
DO0.6
1: Reserved
DO0.7
1: Trip reset
2)
3
DO1.0
1: Motor direction of rotation 1
DO1.1
1: Motor direction of rotation 2
1)
DO1.2
1: Reserved
DO1.3
1: Trip reset
2)
4
DO1.4
1: Motor direction of rotation 1
DO1.5
1: Motor direction of rotation 2
1)
DO1.6
1: Reserved
DO1.7
1: Trip reset
2)
1)
Only in the case of the reversing starter.
2)
You can find information on the trip reset in "Overload protection function (Page 115)".
For additional information, please refer to " Group diagnostics - data set (index) 90