3RA64/3RA65 compact starter with IO-Link
6.4 Parameters
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
109
6.4.4
Operation with operator panel
6.4.4.1
"Operator panel available" parameter
With the "Operator panel available" parameter, you determine whether or not an operator
panel is available for operating the compact starters.
In conjunction with the "Operation at Preset <> Actual Configuration" parameter, operation of
the compact starters with or without operator panel can be configured (see Chapter
"Parameter "Operation at Preset <> Actual Configuration" (Page 109)").
Use of the operator panel is above all useful if manual intervention in an application is an
indispensable requirement for operating the plant, or to enable manual intervention in an
emergency.
The table below shows the values for the "Operator panel available" parameter.
Table 6- 4
"Operator panel available" parameter
Value
Description
Default setting
0
Operator panel available: No
—
1
Operator panel available: Yes
Yes
The "Operator panel available" parameter can only be modified via IO-Link. It cannot be
adjusted at the device.
6.4.4.2
Parameter "Operation at Preset <> Actual Configuration"
The "Operation at Preset <> Actual Configuration" parameter sets the severity level of the
test for the "Operator panel available" parameter.
The table below shows the values for the "Operation at Preset <> Actual Configuration"
parameter.
Table 6- 5
Parameter "Operation at Preset <> Actual Configuration"
Value
Description
Default setting
0
Operation at Preset <> Actual Configuration: disable
—
1
Operation at Preset <> Actual Configuration: enable
enabled
If the parameter value "Operation at Preset <> Actual Configuration" is set to "disable",
operation of the compact starters is only possible if the parameter setting "Operator panel
available" is fulfilled precisely.
If the parameter value "Operation at Preset <> Actual Configuration" is set to "enable",
operation of the compact starters is possible via IO-Link regardless of whether or not an
operator panel is connected.