Accessories
7.14 Operator panel for 3RA64/3RA65 compact starter with IO-Link
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
237
Design
The representation below explains the operator controls and display elements of the
operator panel.
Table 7- 30 Design of the operator panel
(1)
DEVICE LED
The DEVICE LED indicates whether the operator panel is ready to run:
- Green: Operator panel is ready.
- Red: Operator panel is not ready.
(2)
FAULT LED
The FAULT LED indicates whether communication between the compact starter and
the operator panel is functioning properly:
- Red: No communication between motor starter and operator panel.
- Off: Communication between compact starter and operator panel functioning
properly.
(3)
SF button and SF LED
You use the SF button to reset the selected compact starter following an overload
trip.
The SF LED shows a RED light if there is a general fault.
(4)
LED 1 - 4
LEDs 1 to 4 indicate which compact starter has been selected:
- Yellow: Compact starter selected.
- Off: Compact starter not selected.
There is always only one compact starter selected.
(5)
SELECT button
If you press the SELECT button for less than 5 secs, you switch between compact
starter 1 to 4. Gaps in the configuration are skipped. The compact starter selected in
each case is indicated by LEDs 1 to 4.
If you press the SELECT button for more than 5 secs, you switch the entire compact
starter group between jog mode and continuous mode. The change to the operating
mode is confirmed by the "MANUAL MODE" LED flashing.
(6)
Manual Mode button and
LED
You isolate the individual compact starters for manual mode using the MANUAL
MODE button. Isolation of a compact starter is confirmed by the MANUAL MODE
LED flashing.
(7)
Button and LED
You use the
button to drive the currently selected compact starter in direction of
rotation 1 (clockwise). The
LED lights up to confirm this.
(8)
Button and LED
You use the
button to drive the currently selected compact starter in direction of
rotation 2 (counter-clockwise). The
LED lights up to confirm this.
(9)
Slot for enabling block
Plug the enabling block into the slot to take control priority of the compact starters.