Accessories
7.12 AS-i mounting module for 3RA61/3RA62 compact starter
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
223
7.12.6.2
Process data and process images
Logical assignment
The tables below contain the process data and process images for the different AS-i
mounting modules:
Table 7- 22 3RA6970-3A
Compact starter status
Inputs
Outputs
D0
D1
D2
D3
D0
D1
AS-i
mounting
module
ready
1)
Motor ON Group fault Group
warning
Motor
"direction of
rotation 1"
Motor
"direction of
rotation 2"
Normal operation
X
AUX Power OFF,
undervoltage, overvoltage
X
X
2)
X
2)
Direction of rotation 1 switched on
X
X
X
Direction of rotation 2 switched on
X
X
X
Overload tripped
X
X
X
Short circuit tripped
X
X
Direction of rotation 1 and direction
of rotation 2 simultaneously
switched on
X
X
X
X
1)
The AS-i mounting module is ready when
- the AS-i mounting module is snapped onto a functionally ready compact starter and
- AS-i communication and AUX PWR are available.
2)
The bit is only set if the output was already set before the undervoltage or overvoltage was detected.
X: Bit set