Technical data
9.4 Infeed system for 3RA6
SIRIUS 3RA6 compact starter
260
System Manual, 09/2014, NEB560060102000/RS-AA/006
9.4
Infeed system for 3RA6
9.4.1
General technical data
General data
Article number
3RA68.
Standard referred to
IEC 60439-1
Frequency
50/60 Hz
Permissible ambient temperature
1)
Storage/transport
°C
-55 ... +80
Operation
°C
-20 ... +60
2)
1)
You can find additional information on use under higher ambient temperatures in "Infeed system for 3RA6 (Page 30)".
2)
Please note that above 40 °C ambient temperature, the current of the relevant device may be reduced (3RA6, 3RV2).
Rated current I
n
Article number
Left infeed, 50/70 mm² screw terminal with
three slots, outgoing terminals with screw-type
and spring-loaded connection technology, incl.
PE bar
3RA6813-8AB
3RA6813-8AC
A
100
Left infeed, 25/35 mm² screw terminal with
three slots, outgoing terminals with screw-type
and spring-loaded connection technology, incl.
PE bar
3RA6812-8AB
3RA6812-8AC
A
63
Left or right infeed, 25/35 mm², with spring-
loaded connection technology
3RA6830-5AC
A
63
Extension connector
3RA6890-1AB
A
63
Adapter for 3RV1.2 and 3RV2.2 circuit
breakers/motor starter protectors
3RA6890-0BA
A
25
Installation altitude
m
2000 m above sea level
without any restrictions
Vibratory load
f = 4 to 5.8 Hz; d = 15 mm
f = 5.8 to 500 Hz; a = 2 m / s
2
10 cycles
Shock
Half-sine a = 6 m/s
2
at 10 ms
3 pos. and 3 neg. shock in all
axes
Degree of protection
According to IEC/EN 60947-1
IP20 (connection compartment
IP 00)
Touch protection
According to DIN EN 50274
Finger-safe
Rated operating voltage U
e
V
AC 690
Degree of pollution
3