3RA64/3RA65 compact starter with IO-Link
6.2 Description of the hardware
SIRIUS 3RA6 compact starter
94
System Manual, 09/2014, NEB560060102000/RS-AA/006
No. Display element/operator control
Marking
Description
(4)
"Overload trip class" selector
switch
CLASS 10/20
For selecting the overload trip class 10E or 20E.
(5)
"Overload protection function" test
button
TEST
Press this button for at least 5 secs to test the overload
protection function.
(6)
Actuator
•
OFF
•
READY
•
TRIPPED
•
OFF: Compact starter is out of service.
1)
•
READY: Compact starter is ready.
1)
•
TRIPPED: Short circuit or malfunction.
1)
(7)
Connection point for auxiliary
switch block
—
You can plug an auxiliary switch block into the
connection point.
3)
(8)
Control circuit terminal
L+, C/Q, L-
A2-, A1+/Y1, Y2
Connection terminals for IO-Link and
auxiliary voltage and limit switch.
2)
(9)
Main circuit terminals
1L1, 3L2, 5L3
2T1, 4T2, 6T3
Connection terminals and main conductor on the line
side
and outgoing side.
2)
(10) "Device status" LED display
DEVICE
Read the device status of the compact starter:
•
Device OK
1)
•
Overload, process mapping error, general warning,
etc.
1)
•
PRESET configuration not equal to ACTUAL
configuration
4)
(11) "Main contacts closed" LED display STATE ON I
The LED indicates whether the main contacts are open
or closed.
1)
(12) "Group error" LED display
SF
The LED indicates whether a group error is present.
1)
(13) "Short-circuit protection function"
test button
TEST I>>
Press this button to test the short-circuit protection
function.
(14) "Malfunction" mechanical display
RLT 0%
Indicates either that the compact starter is in order or
there is a malfunction.
1)
(15) Warning notice
—
—
(16) Interface for connecting cable
(input)
—
—
(17) Interface for connecting cable
(output)
—
—
1)
You can find information on the device statuses in " Diagnostics (Page 118)".
2)
You can find information on the terminal block pin assignments in "Connecting the
3RA64/3RA65 compact starter with IO-Link (Page 127)".
3)
You can find information on the external auxiliary switch block in "External auxiliary switch
4)
Reference to "Parameter "Operation at Preset <> Actual Configuration" (Page 108)".