Technical data
9.1 3RA6 compact starter
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
247
Article number
3RA61.
3RA62.
3RA64.
3RA65.
Conducted interference
According to IEC/EN 61000-4-6
•
0.15 - 80 MHz
V
10
Conducted HF interference emission
According to CISPR11
•
0.15 - 30 MHz
Class A
Field-based interference
According to IEC/EN 61000-4-3
•
80 - 1000 MHz
V/m 10
Field-based HF interference emission
According to CISPR11
•
30 - 1000 MHz
Class A
Integrated auxiliary and signaling contacts
Direct starter
•
Auxiliary contact
1 NO contact,
1 NC contact
—
•
Overload signaling contact
1 CO contact —
•
Short-circuit signaling contact
1 NO contact —
Reversing starter
•
Auxiliary contact
2 NO contacts —
•
Overload signaling contact
1 CO contact —
•
Short-circuit signaling contact
1 NO contact —
Extendable auxiliary switch block
Direct starter: 1 x auxiliary switch block
2 NO contacts, 2 NC
contacts or 1 NO contact,
and 1 NC contact per
auxiliary switch block
Reversing starter: 1 x auxiliary switch block per direction of rotation
Degree of pollution
3
Safe isolation according to IEC/EN 60947-1
You can find information on safe isolation in "Safe isolation (Page 28)".
max. dimensions
Direct starter
•
Screw-type connection
technology
W x H x D
mm 45 x 170 x 165
•
Spring-loaded connection
technology
W x H x D
mm 45 x 191 x 165
max. dimensions
Reversing starter
•
Screw-type connection
technology
W x H x D
mm 90 x 170 x 165
•
Spring-loaded connection
technology
W x H x D
mm 90 x 191 x 165
Depth starting from standard mounting rail
mm 160