Accessories
7.10 Terminal for a Type E self-protected combination motor controller (UL 508)
SIRIUS 3RA6 compact starter
198
System Manual, 09/2014, NEB560060102000/RS-AA/006
7.10
Terminal for a Type E self-protected combination motor controller
(UL 508)
7.10.1
Scope of supply
Scope of supply of the terminal for Type E
System component
Article number
Figure
Terminal for self-protected
combination motor controller
(Type E) to UL 508
3RV2928-1H
7.10.2
Installing/removal
According to UL 508 (Type E), line-side clearances of 1 and 2 inches are required for Type E
combination motor controllers. If parallel wiring is used for the compact starter, the terminal
for the self-protected combination motor controller (Type E) (3RV2928-1H) must be used.
Note
According to C22.2-14, terminal blocks are not required for installation in accordance with
CSA requirements.
Note
Supply options in accordance with UL 508 (Type E) are still available when compact starters
are installed with a 3RV19 3-phase busbar and the infeed system for 3RA6. For additional
information, please refer to "Infeed in accordance with UL 508 (Type E) (Page 38)".