3RA64/3RA65 compact starter with IO-Link
6.7 Diagnostics
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
121
6.7.2
Diagnostics via IO-Link
Fault types of the 3RA64/3RA65 compact starter
IO-Link errors are mapped to PROFIBUS DP errors. Mapping takes place as described in
IO-Link Integration Part 1 or in accordance with vendor-specific definitions from Siemens.
Table 6- 11 IO-Link event display
PROFIBUS DP error type
Description
(IO-Link error code)
Group error
(SF)
Group
warning (SW)
0x1
00001:
Short-circuit
Circuit breaker tripped
n-release
X
—
0x9
01001:
Error
Contact block defective
X
—
0x11 10001:
No encoder or load voltage
No contact block supply
voltage
X
—
0x18 11000:
Actuator disconnection
Overload tripped
X
—
0x10 10000:
Parameterization error
Target configuration not equal
to actual configuration
X
—
0x1A 11010:
External error
Input shutdown -
Limit direction of rotation 1 or
direction of rotation 2
X
—
0x13 10011:
Communication fault
Configuration change rejected,
PIQ not equal to 0
X
—
—
—
Manual operation connection
aborted
—
X
—
—
Manual operation
—
X
Note
You can read out other diagnostics information via the "Group diagnostics - data set (index)
Note
For IO-Link devices supplied by Siemens, the manufacturer-specific range 0x8CA0 to
0x8CBF will be mapped to the PROFIBUS DP error types 0 to 31.
You can get more information in the manual "IO-Link 4SI SIRIUS Master Electronics Module"
(3RK1005-0LB00-0AA0).