3RA64/3RA65 compact starter with IO-Link
6.2 Description of the hardware
SIRIUS 3RA6 compact starter
96
System Manual, 09/2014, NEB560060102000/RS-AA/006
3RA65 compact starter with IO-Link (reversing starter)
Front view
No. Display element/operator control
(1) "Reset overload trip" button
(2) "Manual/auto reset" selector switch
(3) "Current setting I
e
" setting wheel
(4) "Overload trip class" selector switch
(5) "Overload protection function" test button
(6) Actuator (can be locked in OFF position)
(7a) Connection point for auxiliary switch block (direction of
rotation 1)
(7b) Connection point for auxiliary switch block (direction of
rotation 2)
(8) Control circuit terminals
(9) Main circuit terminals
(10) "Device status" display
(11) "Main contacts closed" display
(12) "Group error" display
(13) "Short-circuit protection function" test button
(14) "Malfunction" mechanical display
(15) "Direction of rotation 1 triggered" LED display
(16) "Direction of rotation 2 triggered" LED display
(17) Warning
Hazardous electrical voltage!
Electrical power can result in electric shock and burns.
For this reason, switch off the power to the system and
the devices before starting to work!
(18) Interface for connecting cable (input)
(19) Interface for connecting cable (output)
Display elements and operator controls of the 3RA65 compact starter (reversing starter) with IO-Link
No.
Display element/operator control Marking
Description
(1)
"Reset overload trip" button
RESET
Press this button to reset the compact starter following an
overload.
(2)
"Manual/auto reset" selector
switch
RESET M/A
For selecting manual or auto reset following an overload.
(3)
"Current setting I
e
" setting wheel Setting ranges
depending on the
article number:
•
0.1 - 0.4 A
•
0.32 - 1.25 A
•
1 - 4 A
•
3 - 12 A
•
8 - 32 A
For selecting the current setting I
e
.