3RA61/3RA62 compact starter
5.2 Description of the hardware
SIRIUS 3RA6 compact starter
System Manual, 09/2014, NEB560060102000/RS-AA/006
49
Configuration of 3RA62 compact starter (reversing starter)
Front view
No.
Display element/operator control
(1)
"Overload trip" mechanical display
(2)
"Reset overload trip" button
(3)
"Manual/auto reset" selector switch
(4)
"Current setting I
e
" setting wheel
(5)
"Overload trip class" selector switch
(6)
"Overload protection function" test button
(7)
Actuator (can be locked in OFF position)
(8a)
Connection point for auxiliary switch block (direction of
rotation 1)
(8b)
Connection point for auxiliary switch block (direction of
rotation 2)
(9)
Control circuit terminals
(10)
Main circuit terminals
(11a) "Main contacts closed" LED display (direction of rotation 1)
(11b) "Main contacts closed" LED display (direction of rotation 2)
(12)
"Control supply voltage present" LED display
(13)
"Short-circuit protection function" test button
(14)
"Malfunction" mechanical display
(15)
"Control supply voltage" connection
(16)
Warnung!
Hazardous electrical voltage!
Electrical power can result in electric shock and burns.
For this reason, switch off the power to the system and the
devices before starting to work!
Display elements and operator controls on the 3RA62 compact starter (reversing starter)
No.
Display element/operator control Marking
Explanation
1)
(1)
"Overload trip" mechanical
display
TRIP
•
No display: Loading on motor is within permissible
range
•
White display: The motor is overloaded.
(2)
"Reset overload trip" button
RESET
Press this button to reset the compact starter following
an overload.
(3)
"Manual/auto reset" selector
switch
RESET M/A
For selecting manual or auto reset following an
overload.