Extended setpoint channel
3.4 Speed setpoint
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
69
Figure 3-4
Flow diagram: Jog 1 and jog 2
Properties
●
If both jog signals are issued at the same time, the current speed is maintained (constant
speed phase).
●
Jog setpoints are approached and exited via the ramp-function generator.
●
Jog is possible from the "Ready to start" state.
●
If ON/OFF1 = "1" and jog are selected simultaneously, ON/OFF1 has priority.
Therefore ON/OFF1 = "1" must not be active for jog to be activated.
●
OFF2 and OFF3 have priority over jog.
●
The switch-on command is issued via p1055 and p1056.
●
The jog speed is defined via p1058 and p1059.
●
The following applies in "Jog mode":
–
The main speed setpoints (r1078) are disabled.
–
The supplementary setpoint 1 (p1155) is disabled.
–
The supplementary setpoint 2 (p1160) is forwarded and added to the current speed.
●
The suppression bandwidths (p1091 ... p1094) and the minimum limit (p1080) in the
setpoint channel are also active in Jog mode.
●
The ramp-function generator cannot be frozen (via p1141) in Jog mode (r0046.31 = 1).