Communication
11.3 Communication via PROFINET IO
Drive functions
828
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
11.3.6.1
Functions supported by PN Gate
PN Gate function overview
Function
Description
Communication channels
•
Cyclic data communication:
– IRT
– RT
•
Acyclic data communication:
- PROFINET alarms
- Read/write data set
- TCP/IP
PROFINET basic services
•
LLDP
•
DCP
•
SNMP
Accesses to process data
Access to the process image:
•
Subslot granular
•
Device granular
Consistency of the cyclic data
Each process data communication cycle can contain a data
component for IRT and RT communication
Network topologies
•
Line
•
Star
•
Tree
Information from the PN Gate
•
Device number
•
Slot number with the associated subslot numbers
•
IO address
•
Diagnostic addresses
•
Module ID (vendor ID and module ID)
•
Send cycles and update times
Activating/deactivating
Activating and deactivating devices via the API without alarm
triggering
Automatic address assignment
Topology-based initialization
Number of IO devices
A maximum of 64 devices
IO area in the controller
•
4096 bytes each, in and out
•
Maximum number of slots: 2048
•
Maximum bytes per slot/module size: 254 bytes
Send cycle
•
RT communication: 1 ms
Update times RT 2
n
with n = 0 to 9x send cycle
•
IRT communication
1 ms - 4
ms in increments of 250 μs minimum send cycle of
1 ms for 32 devices. It is permissible to reduce the data per
device.