Infeed
2.2 Smart Infeed
Drive functions
44
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Figure 2-5
Schematic structure of Smart Infeed chassis
Commissioning
The device connection voltage (p0210) must be parameterized during commissioning.
The Extended Smart Mode can be activated as an option (see Chapter "Extended Smart
Note
In a supply system without regenerative feedback capability (e.g. generators), the
regenerative operation of the infeed must be deactivated via the binector input p3533.
Smart Line Modules do not support kinetic buffering in generator mode.