Vector control
5.9 Vdc control
Drive functions
242
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Remedial measures:
●
activate the V
dc_max
control:
–
Vector control: p1240 = 1 (factory setting)
–
Servo control: p1240 = 1
–
V/f control: p1280 = 1 (factory setting)
●
Inhibit V
dc_max
control:
–
Vector control: p1240 = 0
–
Servo control: p1240 = 0 (factory setting)
–
V/f control: p1280 = 0
●
Activate the V
dc_max
monitoring
–
Vector control: p1240 = 4 or 6
–
Servo control: p1240 = 4 or 6
–
V/f control: p1280 = 4 or 6
WARNING
Unexpected motion of individual drives
If several Motor Modules are supplied from one infeed unit, then if the V
dc_max
control is
incorrectly parameterized, individual drives can accelerate in an uncontrolled fashion -
which can lead to death or severe injury.
•
Only activate the V
dc_max
control for the Motor Module whose drive has the highest
moment of inertia.
•
Inhibit this function for all other Motor Modules, or set this function to monitoring only.