Communication
11.5 Communication via EtherNet/IP
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
885
Table 11- 52 Class Attribute
No. Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Parameter access to drive object 0 (DO 0) is realized via this class.
Example: Read parameter 2050[10] (connector output to interconnect the PZD received from
the fieldbus controller)
Get Attribute single function with the following values:
●
Class = 401 hex
●
Instance = 2050 = 802 hex ≙ parameter number
●
Attribute = 10 = A hex ≙ Index 10
Example: Parameter 1520[0] writing (upper torque limit)
Set Attribute single function with the following values:
●
Class = 401 hex
●
Instance = 1520 = 5F0 hex ≙ parameter number
●
Att
ribute = 0 = 0 hex ≙ index 0
●
Data = 500.0 (value)
Parameter Object, Instance Number: 401 hex ... 43E hex
Supported services
Class
•
Get Attribute All
•
Get Attribute Single
Instance
•
Get Attribute Single
•
Set Attribute Single
Table 11- 53 Class Attribute
No. Service
Type
Name
1
get
UINT16
-
2
get
UINT16
Max slot num
3
get
UINT16
Max slot ID
Parameter access to drive object 0 (DO 0) is realized via this class.
The class structure is analog to 401 hex. Drive object (DO) is selected via the class number.