Infeed
2.1 Active Infeed
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
33
While the identification routine is running, it is not permissible that other loads are switched-
in/switched-out.
Note
In a supply system without regenerative feedback capability (e.g. generators), regenerative
operation must be inhibited via the binector input p3533.
Note
When a Wideband Line Filter is connected, it must be parameterized with p0220 = 1...5. The
temperature sensor must be connected to terminal X21 of the Active Line Module.
The DC link voltage (p3510) can be set within the following limits:
●
Upper limit:
–
Maximum DC link voltage (p0280)
–
Product of line voltage (p0210) and max. step-up factor (r3508)
●
Lower limit: Supply voltage (p0210) multiplied by 1.42
2.1.2
Active Infeed closed-loop control chassis
Figure 2-2
Schematic structure of Active Infeed chassis