Safety Integrated Basic Functions
10.11 Acceptance test and acceptance report
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
721
10.11.1.3
Test scope for specific measures
Scope of partial acceptance tests for specific measures
The measures and points specified in the table refer to the information provided in Section
Content of the partial acceptance test (Page 719).
Table 10- 11 Scope of partial acceptance tests for specific measures
Measure
A) Documentation B) Functional testing
of safety functions
C) Functional testing
of the forced dormant
error detection
D) Functional
testing of actual
value acquisition
E) Conclusion
of the report
Replacement of
the Control Unit
/ power unit
hardware
Yes, Points 1 and
2
No
Yes, only Point 1
Yes, only Point 1 Yes
Replacement of
the Power Mod-
ule or Safe
Brake Relay
Yes, Points 1 and
2
Yes, Points 1 or 2
and 3
Yes, only Point 1
Yes, only Point 1 Yes
Firmware - up-
grade (CU /
power unit /
Sensor Mod-
ules)
Yes, only Point 2
Yes, if new safety
functions are to be
used
Yes
Yes, only Point 1 Yes
Change to a
single parame-
ter of a safety
function (e.g.
SLS limit)
Yes, Points 4 and
5.
Yes, test the appro-
priate function
No
Yes
Yes
Transfer of
project data to
other machines
(series commis-
sioning)
Yes
Yes, but only testing
of the selection of the
safety functions
Yes
Yes
Yes
New firmware
version for
SIMOTION D
Yes, only Point 2
Yes, if new safety
functions are to be
used
Yes
Yes, only Point 1 Yes