Communication
11.6 Communication via SINAMICS Link
Drive functions
896
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Note
For double words, two PZD must be read in succession. To do this, read in a 32 bit setpoint,
which is on PZD 2
+
PZD 3 of the telegram of node 2. Emulate this setpoint on
PZD 2
+
PZD 3 of node 1:
p8872[1] = 2, p8870[1] = 2, p8872[2] = 2, p8870[2] = 3
Activating the SINAMICS Link
To activate SINAMICS Link connections, perform a POWER ON for all nodes.
Without POWER ON, the following can be changed:
●
The assignments of p2051[x]/2061[2x] and the links of the read parameters
r2050[x]/2060[2x]
●
Parameters p8870, p8871, and p8872 In this case, the SINAMICS Link connections can
also be connected via p8842 = 1.
11.6.4
Example
Task
Configure SINAMICS Link for two nodes and transfer the following values:
●
Send data from node 1 to node 2
–
r0898 CO/BO: Control word, sequence control, drive 1 (1 PZD), in the example PZD 1
–
r0079 CO: Total torque setpoint (2 PZD), in the example PZD 2
–
r0021 CO: Smoothed actual speed (2 PZD), in the example PZD 3
●
Send data from node 2 to node 1
–
r0899 CO/BO: Status word, sequence control, drive 2 (1 PZD), in the example PZD 1
●
IF1 is used for SINAMICS Link.
Procedure
1.
For all nodes, set p0009 = 1 to change the device configuration.
2.
For all CBE20 nodes, set the "SINAMICS Link" mode using p8835 = 3.
3.
Limit the maximum number of nodes for all nodes with p8811 = 8. By setting p8811,
parameter p8812[1] is preassigned, and parameter p8836, if necessary, is corrected.