Communication
11.3 Communication via PROFINET IO
Drive functions
806
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
PROFINET IO with IRT (Isochronous Real Time)
Isochronous real time: Real time property of PROFINET IO where IRT telegrams are
transferred deterministically via planned communication paths in a defined sequence to
achieve the best possible synchronism and performance between the IO controller and IO
device (drive unit). IRT is also known as time-scheduled communication whereby knowledge
about the network structure (topology) is utilized. IRT requires special network components
that support planned data transfer.
SINAMICS cycle times of minimum 250
μs (onboard) / 500
μs (CBE20) and a jitter accuracy
of less than 1
μs can be achieved when this transmission method is implemented.
Figure 11-29 Bandwidth distribution/reservation, PROFINET IO
11.3.1.2
Addresses
MAC address
Every Ethernet and therefore every PROFINET interface is assigned a worldwide unique
device identifier in the factory. This 6-byte long device identifier is the MAC address. The
MAC address is divided up as follows:
●
Three bytes for the manufacturer's ID
●
Three bytes for the device identifier (consecutive number)
The MAC address is printed on a label (CBE20) or specified on the type plate (CU320-2 PN
and CU310-2 PN), e.g.: 08-00-06-6B-80-C0.
The Control Units CU320-2 PN and CU310-2 PN have two integrated interfaces:
●
One Ethernet interface
●
One PROFINET interface with two ports
The MAC addresses of the Ethernet and PROFINET interfaces are stamped on the type
plate.