Function modules
8.9 Master/slave function for Active Infeed
Drive functions
550
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Features
●
The "master/slave" function only works in conjunction with Active Line Modules.
●
One Active Line Module is the master and up to three others are slaves.
●
If the master fails, a slave ALM takes on the role of the master.
●
The redundant infeeds can continue functioning normally even if one infeed train has
failed.
●
Electrical isolation between the infeed trains is needed on the line side to prevent
circulating currents caused by non-synchronous pulsing patterns.
●
The entire infeed system supplies a joint DC busbar (DC link).
●
Since the Active Line Module cannot detect whether the DC link is disconnected or a DC-
link fuse has blown, an additional circuit to monitor these states must be installed (DC
breaker checkback function and fuse signaling contacts).
●
The higher-level controller communicates with the CUs and Active Line Modules via
PROFIBUS/PROFINET or analog data. If a higher-level controller is not to be used, the
control signals must be hard-wired (e.g. via TM31).
●
Infeed trains with different outputs can be combined.