
10 Calibration
10.2 Calibrating the Alternating-Voltage Measuring Range
202
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
✧
On the rear plate of the device connect a DC or AC power supply at the terminal block H acc. to
chapter 5.3.2.
✧
Start the device as described in chapter 5.7.
✧
Adjust the following parameters in the
Configure
tab
→
AC measurement
(red marking):
Fig. 10-2
Settings for the Calibrating of an AC Voltage Measuring Range
DANGER
Hazard due to high voltage
Non-observance will lead to death or serious injury.
Work may only be carried out by trained personnel (see Preface) who are familiar with and observe the safety
requirements and precautions.
Work may
never
be carried out if there is any hazardous voltage present.
✧
De-energize the device.
✧
Isolating device:
Connect a suitable isolating device upstream to de-energize the device. The isolating
device must be installed near the device, it must be easily accessible to the user and it must be marked
as an isolating device for the device.
✧
Secure the supply voltage with an approved (UL/IEC) fuse: 1.6 A, type C.
✧
If a melting fuse is used, a suitable approved (UL/IEC) fuse holder has to be used.
SICAM-MMU_7KG9663_US.book Page 202 Monday, December 7, 2015 12:22 PM