10 Calibration
10.2 Calibrating the Alternating-Voltage Measuring Range
201
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
10.2
Calibrating the Alternating-Voltage Measuring Range
Measurement Setup
Fig. 10-1
Measurement Setup for Calibrating the Alternating-Voltage Measuring Range
Calibration is only possible with symmetrical phases (3 x 120°), see figure 10-1.
Measuring Ranges
You can perform the calibration for the following alternating-voltage measuring ranges:
•
AC 63.5 V
•
AC 110 V
•
AC 230 V
•
AC 400 V
Calibration
To calibrate the alternating-voltage measuring ranges, proceed as follows:
✧
Set up the measurement as shown in figure 10-1, depending on the device variant.
Reference
3
N
2
1
Voltage
Output