7 Operation
7.5 Maintenance
139
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
7.5.5.3
Diagnosis I/O Unit Communication
All diagnosis counters are signless 32-bit values (counting maximum: 4 294 967 295).
The diagnosis counters are set to 0 under the following conditions:
•
device restart
•
clicking on
Clear counters
in the input/output window
•
editing and activating the communication type during parameterization
✧
In the navigation window, click the
Diagnosis
menu and then
I/O Unit communication
.
The subdevice is analyzed.
Fig. 7-56
Maintenance Tab, Diagnosis I/O Unit Subdevice
✧
To clear the counters for the subdevice, click
Clear counters
.
All counters of the subdevice are set to 0.
Parameter
•
Operating mode:
I/O mirror client
•
Server IP address:
192.168.0.56
•
Server port:
51000
•
Response timeout:
Default: 30 ms
NOTE
The diagnosis data of the SICAM I/O Unit subdevice are only displayed if this device was selected on the
Configure
tab
→
Administrative
menu
→
I/O Unit subdevice
menu item.
The entry -
none
- is displayed for non-selected protocols.
SICAM-MMU_7KG9663_US.book Page 139 Monday, December 7, 2015 12:22 PM