9 Communication
9.2 Modbus
163
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
9.2.7.6
Register 0113: Group Indications
These registers are write protected. A write attempt will be rejected with exception code 03
(ILLEGAL_DATA_VALUE).
Data type: indication
9.2.7.7
Register 0131: Status of the Binary Outputs
This register is write protected. A write attempt will be rejected with exception code 03
(ILLEGAL_DATA_VALUE).
Data type: indication
Table 9-9
Register 0113: Group Indications
Register
Type of Information
Remark
0113/2
0
Group indication 1
Up to 4 single-point indications can be logically combined to
one group indication.
A maximum of 4 group indications can be parameterized.
0113/2
2
Group indication 2
0113/2
4
Group indication 3
0113/2
6
Group indication 4
0113/2
8
to
0113/2
14
Reserved
= 0
Table 9-10
Register 0131: Status of the Binary Outputs
Register
Type of Information
Remark
0131/2
0
Binary Output B1
Binary output B1 at terminal block G
0131/2
2
Binary Output B2
Binary output B2 at terminal block G
0131/2
4
to
0131/2
14
Reserved
= 0