10 Calibration
10.3 Calibrating the Alternating Current Measuring Range
206
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
✧
Click the
Maintenance
tab on the User Interface.
The
Maintenance
tab opens.
✧
Click the
AC Calibration
element in the navigation window.
The
AC Calibration
input/output window opens.
Fig. 10-6
Calibrating the Alternating Current Measuring Range
✧
Check which measuring range is presently used in the input/output window at
Actual measuring range
is: 63.5 V/1 A
.
✧
Enter the maintenance password into the
Password
field.
✧
Enter the reference current 1.0 A that is generated by the measurement setup into the
Reference current
field.
✧
Click the
Calibrate current
button.
The device executes the calibration and the lower field of the input/output window automatically displays
the updated calibration date.
✧
Check the calibrating values in the
Value View
tab
→
AC operational values
.
✧
Carry out the calibration for the current measurement range AC 5 A in accordance of the described work
steps.