7 Operation
7.3 Configuration of the Device
103
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
7.3.3.2
Automation Functions
7.3.3.2.1
Limit Settings
In the
Select automation functions
menu you can set upper or lower limits for up to 16 measured values.
Limit violations of the upper or lower value range can be output as indications. Up to 4 limit value violations can
be signaled at the device via the two binary outputs and the LEDs H1 and H2. Furthermore, all 16 limit violations
can be sent to peripheral devices via Ethernet.
The programmable limits are divided into two groups
Measurand limits 1-8
and
Measurand limits 9-16
. The
parameterization is identical for all limits.
Default Settings and Setting Ranges of the Limits
Table 7-5
Limit Settings
Parameter
Default Setting
Setting Range
Measurand
-none-
Acc. to list box
Limit
0.0
-1 000 000 000 to 1 000 000 000 (unit)
Limit type
Lower
Lower
Upper
Hysteresis (%)
1.0
0.0 to 10.0
Violation indication
Limit Violation x
(x = 1 to 16)
The name of the limit violation indication is
customizable.