9 Communication
9.2 Modbus
151
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Parameterization
The following parameters can be set for the Modbus TCP bus protocol, see also chapter 7.3.4.2:
Number of Connections
Up to four TCP connections are possible:
•
Without user port number:
4 connections via standard port 502
•
With user port number:
2 connections via standard port 502 and 2 connections via the
user port
Table 9-2
Modbus TCP Settings
Parameter
Default Setting
Settings
IP address
192.168.0.55
any,
0.0.0.0 for DHCP
Subnet mask
255.255.255.0
Any
Default gateway
192.168.0.1
Any
Bus protocol
Modbus TCP
-
Use a user-port number
no
no
yes
User-port number
(only if
Use a user-port number
yes
has been
parameterized)
10000
10000 to 65535
Access rights for user port 502
Full
Full
Read only
Access rights for user port
(only if
Use a user-port number
yes
has been
parameterized)
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 * 100 ms
0 s = none
100 ms to 6 553 400 ms
SICAM-MMU_7KG9663_US.book Page 151 Monday, December 7, 2015 12:22 PM