7.3.4
Setting Administrative Parameters
In the
Configure
tab you can view, and if necessary, edit the administrative settings. You can select the pa-
rameters in the
Administrative
menu in the navigation window. You can enter the settings in the input/output
windows
Time synchronization
,
Communication Ethernet
,
IEC 60870-5-104
(only if this bus protocol was
selected under
Communication Ethernet
), and
Device and language
.
7.3.4.1
Time Synchronization
Default Settings and Setting Ranges of the Time Synchronization
NOTE
Observe the procedure for the device configuration described in chapter 7.3.1 when setting the administrative
parameters.
Table 7-7
Time Synchronization Settings
Parameter
Default Setting
Setting Range
Source time synchronization
Internal
Acc. to list box
Time zone offset to UTC
+00:00
-12 to +13 (hours)
(in increments of 0.5 h)
Daylight Saving Time switchover
yes
no
yes
DST offset to UTC
+01:00
0 to + 2 (hours)
(in increments of 0.5 h)
Start of DST
March
Last week
Sunday
02:00 AM
Acc. to list boxes
End of DST
October
Last week
Sunday
03:00 AM
Acc. to list boxes
Additional Parameters if the Source is Ethernet NTP
(Modbus TCP and IEC 60870-5-104)
Primary NTP server IP address
192.168.0.254
Any
Secondary NTP server IP address
192.168.0.253
Any
No polling of the NTP server if
0.0.0.0 was entered
Error indication after
10 min
2 min to 120 min