14 Operational Indications
241
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Indication x from
Remote
(x = 1 to 8)
Status of the indications that can be
set to control the LEDs and the
binary outputs via the communica-
tion.
Indication on: ON
Indication off: OFF
Message invalid: Not yet updated via the communication
or again invalid via the communication
Rotating Field
Clockwise
Indication of rotation voltage
Indication ON: Phase sequence Va-Vb-Vc, rotation
clockwise
Indication OFF: Phase sequence Va-Vc-Vb, (2 phases
interchanged); rotation anti-clockwise
Indication invalid: Direction of rotation can not calculated
(e.g. no voltage applied)
Group indication x
(x = 1 through 4)
Up to 4 single-point indications can
be logically combined to one group
indication.
A total of 4 group indications can be parameterized.
IEC 60870-5-104 OK
Communication via protocol
IEC 60870-5-104 is correct (set to
OFF
after start).
All indications in the device that are
controlled via IEC 60870-5-104 are
set to invalid if the indication
IEC 60870-5-104 OK
switches to
OFF
. This causes the associated
binary outputs of the device and
the outputs of any connected
SICAM I/O Unit to be set to invalid,
too.
The indication
IEC 60870-5-
104 OK
is entered as operational
indication and can be routed to an
LED of the device.
Parameter: Enable redundancy = no
Indication on: Changes to ON when IEC 60870-5-104
stack is successfully started and the IEC master has es-
tablished a TCP connection to the SICAM MMU device.
Indication off: Changes to OFF when the TCP connec-
tion between IEC master and the SICAM MMU device is
interrupted.
Parameter: Enable redundancy = yes
Indication on: If the IEC 60870-5-4 stack was started
successfully and at least one of the IEC 60870-5-4
masters has established a Modbus TCP connection to
the SICAM MMU, regardless of whether the connection
was started or stopped.
Indication off: If all Modbus TCP connections between
IEC 60870-5-4 masters and the SICAM MMU have
been interrupted.
Binary input x-N I/O
Unit (x = 1 through 3)
Binary input terminal N at connect-
ed I/O Unit
Indication on: ON
Indication off: OFF
Indication invalid: no I/O Unit connected or communica-
tion error
Binary input x-P I/O
Unit (x = 1 through 3)
Binary input terminal P at connect-
ed I/O Unit
Binary output x-N I/O
Unit (x = 1 through 3)
Binary output terminal N at con-
nected I/O Unit
Indication on: ON
Indication off: OFF
Indication invalid: no I/O Unit connected or communica-
tion error
Binary output x-P I/O
Unit (x = 1 through 3)
Binary output terminal P at con-
nected I/O Unit
Indication
Description
Notes
SICAM-MMU_7KG9663_US.book Page 241 Monday, December 7, 2015 12:22 PM