9 Communication
9.2 Modbus
162
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
9.2.7.5
Register 0111 and 0112: Limit-Violation Indications
These registers are write protected. A write attempt will be rejected with exception code 03
(ILLEGAL_DATA_VALUE).
Data type: indication
Table 9-8
Register 0111 and 0112: Limit-Violation Indications
Register
Type of Information
Remark
0111/2
0
Limit Violation 1
An indication is output (= 1) if a measured value has exceed-
ed or fallen below a configured limit value, see
chapter 7.3.3.2.
0111/2
2
Limit Violation 2
0111/2
4
Limit Violation 3
0111/2
6
Limit Violation 4
0111/2
8
Limit Violation 5
0111/2
10
Limit Violation 6
0111/2
12
Limit Violation 7
0111/2
14
Limit Violation 8
0112/2
0
Limit Violation 9
An indication is output (= 1) if a measured value has exceed-
ed or fallen below a configured limit value, see
chapter 7.3.3.2.
0112/2
2
Limit Violation 10
0112/2
4
Limit Violation 11
0112/2
6
Limit Violation 12
0112/2
8
Limit Violation 13
0112/2
10
Limit Violation 14
0112/2
12
Limit Violation 15
0112/2
14
Limit Violation 16
SICAM-MMU_7KG9663_US.book Page 162 Monday, December 7, 2015 12:22 PM