7 Operation
7.3 Configuration of the Device
96
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
To change the parameters of the measured-value acquisition, proceed as follows:
✧
In the navigation window, select the
Operational
menu, then the
Process connections
submenu and
click the
AC measurement
menu item.
Fig. 7-20
Configure Tab, AC Measurement Input/output Window
✧
Enter the desired values in the fields and select the parameters in the list boxes and option fields as
described in Table 7-2.
✧
If you are not using a voltage transformer and/or current transformer between the measurement object
and SICAM MMU, click
no
in the respective option field. The associated fields for primary and secondary
values are hidden in this case.
✧
In the
Calculate VN
option field, select whether to calculate (
yes
) or measure (
no
) the voltage of the
neutral conductor.
✧
Click
Send
.
The parameters are transmitted to the device but not enabled yet (passive set of parameters).
✧
If you do not want to make any additional settings, continue with the
activation
of the device configuration
Activating the Set of Parameters
. If you want to change other settings, enter the changes
and then enable the device configuration as described in
Activating the Set of Parameters
.
NOTE
The option field
Calculate VN
is only visible in the device variants SICAM MMU 7KG9663-1AA00-xAA0 (de-
vices with a voltage divider at the voltage measuring inputs).
The voltage in the neutral conductor is calculated if it is grounded (standard).
The voltage in the neutral conductor is measured if b is grounded (special connection type).