13 Technical Data
13.1 General Device Data
230
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Inputs for Alternating Current Measurements (Connector Block E)
Binary Outputs (Connector Block G)
Input AC currents
Rated input current range
1 A
5 A
Operat. measurem. uncertainly acc. to IEC 60688:
±0.1 %
Max. input current
2 x rated input AC current
Power consumption per input
at 1 A
1 mVA
at 5 A
2.5 mVA
Further information about the current measurement inputs
Permissible power frequency
45 Hz to 65 Hz
Max. rated input voltage
150 V
Measuring error (with calibration) at 23 °C ± 1 °C 50 Hz
or 60 Hz
Typically 0.1 % at rated input current
Thermal stability
10 A continuous
100 A for max. 1 s according to IEC 60688
Maximum switching voltage
Alternating voltage
230 V
Direct voltage
250 V
Maximum currents
Maximum continuous contact current
100 mA
Maximum pulse current for 0.1 s
300 mA
Further information about the binary outputs
Internal impedance
35
Ω
Admissible switching frequency
10 Hz
Number of switching cycles
Unlimited
SICAM-MMU_7KG9663_US.book Page 230 Monday, December 7, 2015 12:22 PM