15 Operating Parameters
15.3 Administrative
252
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Measured Value Data Group
1)
Only relevant, if threshold method not equal -
none-
2)
Data points that are selected as
blocked
will not be transmitted as spontaneous event any more, if changes
occur. They are marked as
quality code
=
blocked
in the cyclic telegrams and general interrogation.
Parameter
Default Setting
Setting Range
Measured value data
group
AC voltage
AC voltage
AC current
Active power
Reactive power
Apparent power
Angle
Active power factor cos
φ
Frequency
Harmonics V magnitude
Harmonics I magnitude
Harmonics V angle
Harmonics I angle
Percentage value
Threshold processing (per Measured Value Data Group)
Threshold method
Fixed
-none-
Fixed
Integrated
Fixed and integrated
Threshold calculation
1)
Absolute (in unit of the measured
value)
Absolute (in unit of the measured
value)
Relative (in percentage related to
the last transmitted measured value)
Threshold value
1)
AC voltage:
5 V
AC current:
0.05 A
Active power:
2 W
Reactive power:
2 var
Apparent power:
2 VA
Angle:
3°
Active power factor cos
φ
:
0.05
Frequency:
0.2 Hz
Harmonics V magnitude:
0.1 V
Harmonics I magnitude:
0.05 A
Harmonics V angle:
3°
Harmonics I angle:
3°
Percentage value:
0.5 %
Absolute threshold calculation:
Depending on the selected
Measured value data group
Relative threshold calculation:
0 % to 100 %
Data Points (per Measured Value Data Group)
Information name
Values cannot be parameterized.
Address (IOA)
For information;
Values cannot be parameterized.
Transmission
enable
blocked
2)
enable
SICAM-MMU_7KG9663_US.book Page 252 Monday, December 7, 2015 12:22 PM