9 Communication
9.2 Modbus
167
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
9.2.7.12 Measured Values
9.2.7.12.1
Register 0201 to 0280: Measured Values
These registers are write protected. A write attempt will be rejected with exception code 03
(ILLEGAL_DATA_VALUE).
Data type: Measured value
Table 9-15
Registers 0201 to 0280: Measured Values
Register
Measured Value
Remark
Unit
0201
Va
Voltage a-N
V
0203
Vb
Voltage b-N
V
0205
Vc
Voltage c-N
V
0207
VN
Voltage neutral conductor
V
0209
Ia
Current a
A
0211
Ib
Current b
A
0213
Ic
Current c
A
0215
IN
Current neutral conductor
A
0217
Vab
Voltage a-b
V
0219
Vbc
Voltage b-c
V
0221
Vca
Voltage c-a
V
0223
Vavg
Mean value of voltage (P-N)
V
0225
Iavg
Mean value of currents
A
0227
Pa
Active power a
W
0229
Pb
Active power b
W
0231
Pc
Active power c
W
0233
P
Active power
W
0235
Qa
Reactive power a
var
0237
Qb
Reactive power b
var
0239
Qc
Reactive power c
var
0241
Q
Reactive Power
var
SICAM-MMU_7KG9663_US.book Page 167 Monday, December 7, 2015 12:22 PM