7 Operation
7.3 Configuration of the Device
99
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
Parameterizing an Indication
Select the desired parameters for an
indication
in the list boxes and option fields (see figure 7-21, example
terminal G1/3) as described in Table 7-3.
The
Operating mode
list box contains the following options:
−
Persistent
: The binary output has the status ON or OFF. If the indication becomes invalid, the binary
output continues to maintain its current status.
Fig. 7-22
Persistent
−
Persistent with fail save
: If the indication becomes invalid, the binary output switches into the OFF
state, that is if
Source inverted
=
no
, or it switches into the ON state if
Source inverted
=
yes
.
Fig. 7-23
Persistent with Fail Save
−
Pulse
without retrigger: This indication is output as pulse. If the indication changes again while the
output pulse is ON, the pulse output time is not restarted. This means that a change of the indication
during the pulse output will be ignored.
Fig. 7-24
Pulse without Retrigger
NOTE
If you select
-none-
as the
Source type
of an
Indication
and/or
Energy counter
, the corresponding binary
output is inactive.
invalid
Binary output
inverted
Indication
Indication
Output
Binary output
not inverted
invalid
ON
Output
ON
OFF
OFF
ON
OFF
invalid
Binary output
inverted
Indication
Indication
Output
Binary output
not inverted
invalid
ON
Output
ON
OFF
OFF
ON
OFF
Indication
Output
ON
Binary output with
„Source inverted“ = no
OFF
ON
OFF
Output time
Indication
Indication
Indication
Output
Output
Output
Output
Output
Binary output with
„Source inverted“ = yes
ON
OFF
Output time