7 Operation
7.3 Configuration of the Device
112
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
7.3.4.2.2
Ethernet Communication with Modbus TCP Bus Protocol
Default Settings and Setting Ranges of the Ethernet Communication with Modbus TCP Bus Protocol
1)
After enabling the parameter changes, any currently active Modbus TCP connections will be closed. The
Modbus TCP client must later reopen these connections.
To edit the settings of the Ethernet communication with Modbus TCP bus protocol, proceed as follows:
✧
In the navigation window, click the
Administrative
menu and then
Communication Ethernet
.
✧
Select the entry
Modbus TCP
from the
Bus protocol
list box.
Fig. 7-36
Configure Tab, Communication Ethernet, Bus Protocol Modbus TCP
Table 7-9
Settings of the Ethernet Communication with Modbus TCP Bus Protocol
Parameter
Default Setting
Setting Range
Use a user-port number
1)
no
no
yes
User-port number
1)
(can only be set when
Use a user-port
number
is parameterized with
yes
)
10000
10000 to 65535
Access rights for user port
(can only be set when
Use a user-port
number
is parameterized with
yes
)
Full
Full
Read only
Access rights for port 502
Full
Full
Read only
Keep Alive time
10 s
0 s = switch off
1 s to 65 535 s
Communication supervision time
600 * 100 ms
0 s = none
100 ms to 6 553 400 ms