7 Operation
7.3 Configuration of the Device
120
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
7.3.4.3
SICAM I/O Unit (Subdevice)
7.3.4.3.1
SICAM I/O Unit (Subdevice) - Setting Parameters in the SICAM MMU
Default Settings and Setting Ranges
1)
If you have selected
no
, no settings can be made.
Table 7-12
Settings of the SICAM I/O Unit (Subdevice)
Parameter
Default Setting
Setting Range
I/O Unit connected
no
no
1)
yes
Server IP address
192.168.0.56
Any
Server port
51000
10000 to 65535
Response timeout
3 * 10 ms
0 ms = invalide
10 ms to 60 000 ms
Source of output 1-N
Indication 3 from remote
Acc. to list box
(see chapter 15)
Source of output 2-N
Indication 4 from remote
Source of output 3-N
Indication 5 from remote
Source of output 1-P
Indication 6 from remote
Source of output 2-P
Indication 7 from remote
Source of output 3-P
Indication 8 from remote
NOTE
The 6 indications
Source of output 1-x
to
Source of output 3-P
can also be remote-controlled via Modbus
TCP or IEC 60870-5-104 Master instead of setting the parameters in the device.
NOTE
Indication 1 from remote
and
Indication 2 from remote
are provided for controlling the two binary outputs
of the SICAM MMU.
SICAM-MMU_7KG9663_US.book Page 120 Monday, December 7, 2015 12:22 PM