9 Communication
9.2 Modbus
165
SICAM MMU 7KG9663, Device Manual
E50417-H1040-C514-A3, Edition 01.2016
9.2.7.9
Register 0136: Status of Binary Outputs of SICAM I/O Unit (Subdevice)
This register is write protected. A write attempt will be rejected with exception code 03
(ILLEGAL_DATA_VALUE).
Data type: indication
9.2.7.10 Register 0141: Indications of the Communication -1-
Data type: controllable indications
Table 9-12
Register 0136: Status of Binary Outputs of SICAM I/O Unit (Subdevice)
Register
Type of Information
Remark
0136/2
0
Binary output 1-N I/O Unit
(terminal N1/2)
The statuses of the binary outputs are read from
the SICAM I/O Unit:
Value = 0 and status = invalid if indication:
External I/O Unit OK
= 0
(communication to the SICAM I/O Unit interrupted)
0136/2
2
Binary output 2-N I/O Unit
(terminal N3/4)
0136/2
4
Binary output 3-N I/O Unit
(terminal N6/7)
0136/2
6
Binary output 1-P I/O Unit
(terminal P1/2)
0136/2
8
Binary output 2-P I/O Unit
(terminal P3/4)
0136/2
10
Binary output 3-P I/O Unit
(terminal P6/7)
0136/2
12
Reserved
= 0
0136/2
14
Reserved
= 0
Table 9-13
Register 0141: Indications of the Communication
Register
Type of Information
Remark
0141/2
0
Indication 1 from Remote
For controlling the binary outputs via the communication
Can also be used to control LEDs or can be integrated into
a group indication.
0141/2
2
Indication 2 from Remote
0141/2
4
to
0141/2
12
Reserved
= 0
0141/2
14
Reset Energy
0
→
1: Resets the energy counters
SICAM-MMU_7KG9663_US.book Page 165 Monday, December 7, 2015 12:22 PM