Settings
You have the following options in the
Settings
area:
•
Set the display brightness and contrast.
Complementary information
The display language is set using Safety Designer during configuration. The display
language and the configuration cannot be changed using the pushbuttons on the
display.
11.3
Error indication on the display
Overview
If there is an error, the display shows a warning symbol, a type of error and an error
code on a red flashing background.
Figure 69: Error display
•
The two-character error type will help you during troubleshooting.
•
The eight-character error code in the bottom line helps SICK support during the
detailed error analysis.
•
By pressing any pushbutton, you will obtain more information about the error and
for troubleshooting. You can use the arrow buttons to change to further pages with
additional information.
•
You will find detailed information in Safety Designer’s message history about the
individual errors and information about events not shown by the display.
Error indication on the display
Table 23: Error types
Error type
Brief description
Cause
Troubleshooting
C1
Faulty configuration
The configuration is faulty.
b
Reconfigure the device.
C2
Incompatible configura‐
tion
The configuration in the system plug
does not match the device’s func‐
tionality.
b
Check device variant.
b
Replace or reconfigure the
device.
C3
Incompatible firmware
The configuration in the system plug
does not match the device’s firm‐
ware version.
b
Check the firmware version of
the device.
b
Replace or reconfigure the
device.
E1
Error in the safety laser
scanner
The safety laser scanner has an
internal error.
b
Perform a device restart using
the display or Safety Designer or
interrupt the voltage supply for at
least two seconds.
b
Replace the safety laser scanner
and send it to the manufacturer
for repair.