Figure 67: Replacing the system plug
5.
Carefully insert the new system plug into the safety laser scanner.
6.
Screw in the system plug using the captive screws. Tightening torque: 2.25 Nm …
2.75 Nm.
7.
Reconnect the connecting cables to the system plug.
8.
Configure the safety laser scanner,
.
9.
Perform commissioning again, taking particular care to conduct all of the thorough
checks described,
.
Complementary information
If a system plug has already been used on a device that has a different interface for
integrating it into the controller, this system plug can no longer be used on a PROFINET
device.
10.6
Regular thorough check
The thorough check is intended to ensure that the safety functions are fulfilling their
planned purpose and whether persons are being adequately protected.
b
Carry out the checks specified in the test plan of the manufacturer of the machine
and the operating entity.
MAINTENANCE
10
8027931/2022-10-24 | SICK
O P E R A T I N G I N S T R U C T I O N S | outdoorScan3 – PROFINET
123
Subject to change without notice