Design
D - 25
(4)Additional sound from reflection
●
Operation sound from an outdoor unit has the characteristic that it will be reflected from the walls of the
building and ground surfaces. At the reception point these reflections will be received, adding to the sound
level of the system.
●
The sound received at the reception point is the sum [reception point
]
=
[
sound directly transmitted from the
source
]
+
[
reflected sound
]
.
The reflected sound is obtained by setting a virtual sound source A’, and estimating the sound level at B from
the sound source at A’(the distance attenuation from A’~B is subtracted).
See the section on combining sounds, for information on how to add the direct sound and the reflected sound.
(5) Combining sounds
By combining the sound from several outdoor units, it is possible
to know the sound level at a reception point.
The combination of sound from n units L
1
, L
2
, ...
L
n
is expressed
by the following formula.
If the combined sound is L, then
For example, adding 61 phons and 62 phons gives,
This formula is also used for combining the sounds from
multiple outdoor units.
This is the procedure for calculating the sound level,
however, it is easier to use graphs, so graphs have
been prepared for this purpose.
<Calculation example 1>
Combine L
1
= 62[dB] and L
2
= 61[dB]. L
1
- L
2
= 62-61 =
1[dB]. From Figure 5 the correction value is 2.5[dB].
62+2.5=64.5 [dB]. Therefore the combined sound level is
64.5[dB].
<Calculation example 2>
To combine 60[dB], 64[dB], 63[dB], and 65[dB], firstly the
values are arranged in order of magnitude.
65[dB]
.
64[dB]
.
63[dB]
.
60[dB]
Firstly combine 65[dB] and 64[dB],
difference is 65-64=1[dB], correction value is 2.5 dB, so
65+2.5= 67.5[dB]. Next, 67.5[dB] and 63[dB] are
combined, difference is 4.5[dB], so the correction value is
1.3[dB], so 67.5+1.3=68.8[dB].
In the same way, 68.8[dB] and 60[dB] have a level
difference of 8.8[dB], correction value is 0.5[dB].
Therefore 68.8+0.5=69.3[dB].
This is the result of adding the four sounds.
Figure 5 Combined sound correction values
L
1
-L
2
(dB or phon)
Correction value (dB or phon)
adding L
1
and L
2
(L
1
>L
2
)
L=L
1
+ correction value
(for a correction value corresponding
to (L
1
-L
2
) add to L
1
)
L=10 log
10
(10 +10 + +10 )
.......
10
L
1
10
L
2
10
L
3
L=10 log
10
(10 +10 )=64.5db
10
61
10
62
Fig.6 Addition of reflected sound (wall surface)
Fig. 7 Addition of reflected sound(ground surface)
6. Sound-proofing measures
Summary of Contents for SGP-E120J2GU2
Page 49: ...Design D 5 2 Operating temperature ranges for heating and cooling Cooling Heating ...
Page 87: ...Design D 43 8 Salt resistant specification ...
Page 109: ...Construction E 22 4 Outdoor unit installation and construction ...
Page 110: ...Construction E 23 4 Outdoor unit installation and construction ...
Page 111: ...Construction E 24 4 Outdoor unit installation and construction ...
Page 112: ...Construction E 25 4 Outdoor unit installation and construction ...
Page 113: ...Construction E 26 4 Outdoor unit installation and construction ...
Page 114: ...Construction E 27 4 Outdoor unit installation and construction ...
Page 115: ...Construction E 28 4 Outdoor unit installation and construction ...
Page 116: ...Construction E 29 4 Outdoor unit installation and construction ...
Page 117: ...Construction E 30 4 Outdoor unit installation and construction ...
Page 118: ...Construction E 31 4 Outdoor unit installation and construction ...
Page 119: ...Construction E 32 4 Outdoor unit installation and construction ...
Page 120: ...Construction E 33 4 Outdoor unit installation and construction ...
Page 121: ...Construction E 34 4 Outdoor unit installation and construction ...
Page 122: ...Construction E 35 4 Outdoor unit installation and construction ...
Page 123: ...Construction E 36 4 Outdoor unit installation and construction ...
Page 124: ...Construction E 37 4 Outdoor unit installation and construction ...
Page 127: ...Construction E 40 5 Commissioning ...
Page 128: ...Construction E 41 5 Commissioning ...
Page 129: ...Construction E 42 5 Commissioning ...
Page 130: ...Construction E 43 5 Commissioning ...
Page 131: ...Construction E 44 5 Commissioning ...
Page 132: ...Construction E 45 5 Commissioning ...
Page 133: ...Construction E 46 5 Commissioning ...
Page 134: ...Construction E 47 5 Commissioning ...
Page 135: ...Construction E 48 5 Commissioning ...
Page 136: ...Construction E 49 5 Commissioning ...
Page 137: ...Construction E 50 5 Commissioning ...
Page 138: ...Construction E 51 5 Commissioning ...
Page 139: ...Construction E 52 5 Commissioning ...
Page 140: ...Construction E 53 5 Commissioning ...
Page 141: ...Construction E 54 5 Commissioning ...
Page 142: ...Construction E 55 5 Commissioning ...
Page 143: ...Separately Contents 1 Parts for the outdoor unit 1 Exhaust extension kit F 2 F 1 ...
Page 150: ...Periodicinspection G 3 1 Periodic maintenance contract 70 90 Type 120 150 190 Type ...
Page 155: ...Water heat exchange unit H 5 3 External view ...
Page 158: ...Water heat exchange unit H 8 4 Specification 2 External dimension diagram ...
Page 161: ...Water heat exchange unit H 11 4 Specification ...