Design
D - 27
Table 1 Sound-proofing calculation sheet (filled in example)
Frequency
Hz 63
125 250 500 1000 2000 4000 8000
From the operating sound characteristics diagram in the outdoor unit manual
1)Operating sound of outdoor unit
dB
69 66 62 59 56 49.5 45 41.5
From distance attenuation
2) Distance attenuation
dB
From Figure 1, attenuation of unit operating sound –22
Figure 2 Refraction attenuation quantity,
sound path difference d=A+B-d
δ
:0.5
3) Refraction attenuation
dB
-3.5 -5 -6.5 -9 -12 -15 -18 -21
Figure 6 additional sound due to reflections (wall)
4) Increase for reflections (wall
surface)
dB
By calculation or the simplified method, the combined two sounds MAX value is +3
Figure 7 additional sound due to reflection (ground surface)
5) Increase for reflections(ground
surface)
dB
By calculation or the simplified method, the combined two sounds MAX value is +3
6) Sub-total
dB
49.5
45 39.5 34 28 18.5 11 4.5
Conversion factors for A characteristic
7) Overall A characteristic correction
factor
dB
-26 -16 -9 -3 0 +1 +1 -1
8)A characteristic
dB(A)
23.5
29
30.5 31 28 19.5 12 3.5
Frequency
Hz 63 125 250 500 1000 2000 4000 8000
From the operating sound characteristics diagram in the outdoor unit manual
1) outdoor unit operation sound
dB
Distance attenuation
2) distance attenuation
dB
Distance attenuation value:
Refraction attenuation sound path difference d=A+B d
δ
:
3) Refraction attenuation
dB
Additional sound due to reflections (wall)
4) Additional sound due to reflection
(wall surface)
dB
By calculation or the simplified method, the combined two sounds MAX value is +3
Figure 7 additional sound due to reflections (ground surface)
5) Additional sound due to reflection
(ground surface)
dB
By calculation or the simplified method, the combined two sounds MAX value is +3
6)
Sub-total
dB
Conversion factors for A characteristic
7) Overall A characteristic conversion
factor
dB
-26 -16 -9 -
-
3 0 +1
+1 -1
8)
A
characteristic
dB(A)
When the calculation in the above table is complete, the overall A characteristic is calculated at the reception point.
(calculate in order of largest sound level). When the overall A characteristic is calculated, combine this with the
background noise level to obtain the total sound level at the reception point.
When the calculation in Table 1 is completed, the overall A characteristic is calculated.
(8)Sound-proofing calculation sheet (example)
6. Sound-proofing measures
Summary of Contents for SGP-E120J2GU2
Page 49: ...Design D 5 2 Operating temperature ranges for heating and cooling Cooling Heating ...
Page 87: ...Design D 43 8 Salt resistant specification ...
Page 109: ...Construction E 22 4 Outdoor unit installation and construction ...
Page 110: ...Construction E 23 4 Outdoor unit installation and construction ...
Page 111: ...Construction E 24 4 Outdoor unit installation and construction ...
Page 112: ...Construction E 25 4 Outdoor unit installation and construction ...
Page 113: ...Construction E 26 4 Outdoor unit installation and construction ...
Page 114: ...Construction E 27 4 Outdoor unit installation and construction ...
Page 115: ...Construction E 28 4 Outdoor unit installation and construction ...
Page 116: ...Construction E 29 4 Outdoor unit installation and construction ...
Page 117: ...Construction E 30 4 Outdoor unit installation and construction ...
Page 118: ...Construction E 31 4 Outdoor unit installation and construction ...
Page 119: ...Construction E 32 4 Outdoor unit installation and construction ...
Page 120: ...Construction E 33 4 Outdoor unit installation and construction ...
Page 121: ...Construction E 34 4 Outdoor unit installation and construction ...
Page 122: ...Construction E 35 4 Outdoor unit installation and construction ...
Page 123: ...Construction E 36 4 Outdoor unit installation and construction ...
Page 124: ...Construction E 37 4 Outdoor unit installation and construction ...
Page 127: ...Construction E 40 5 Commissioning ...
Page 128: ...Construction E 41 5 Commissioning ...
Page 129: ...Construction E 42 5 Commissioning ...
Page 130: ...Construction E 43 5 Commissioning ...
Page 131: ...Construction E 44 5 Commissioning ...
Page 132: ...Construction E 45 5 Commissioning ...
Page 133: ...Construction E 46 5 Commissioning ...
Page 134: ...Construction E 47 5 Commissioning ...
Page 135: ...Construction E 48 5 Commissioning ...
Page 136: ...Construction E 49 5 Commissioning ...
Page 137: ...Construction E 50 5 Commissioning ...
Page 138: ...Construction E 51 5 Commissioning ...
Page 139: ...Construction E 52 5 Commissioning ...
Page 140: ...Construction E 53 5 Commissioning ...
Page 141: ...Construction E 54 5 Commissioning ...
Page 142: ...Construction E 55 5 Commissioning ...
Page 143: ...Separately Contents 1 Parts for the outdoor unit 1 Exhaust extension kit F 2 F 1 ...
Page 150: ...Periodicinspection G 3 1 Periodic maintenance contract 70 90 Type 120 150 190 Type ...
Page 155: ...Water heat exchange unit H 5 3 External view ...
Page 158: ...Water heat exchange unit H 8 4 Specification 2 External dimension diagram ...
Page 161: ...Water heat exchange unit H 11 4 Specification ...