Water heat exchange unit
H - 15
5. Control
(4) Abnormality display
●
Reset method [common for to ]: After removing the cause of the abnormality, automatic recovery or reset button
1
Sensor abnormality (determined on the water heat exchanger side)
Water heat exchanger unit refrigerant inlet temperature (primary or secondary) [F01]
• Detection method Wire break (-30
o
C t) or short circuit (130
o
C t)
Abnormality of water heat exchanger unit freeze prevention sensor(primary or secondary)[F02]
• Detection method Wire break (-30
o
C t) or short circuit (130
o
C t)
Abnormality of water heat exchanger unit refrigerant outlet
temperature (primary or secondary)[F03]
• Detection method Wire break (-30
o
C t) or short circuit ((130
o
C t)
Abnormality of hot and cold water inlet temperature sensor [F10]
• Detection method Wire break (-30
o
C t) or short circuit (80
o
C t)
Abnormality of hot and cold water outlet temperature sensor [F11]
• Detection method Wire break (-30
o
C t) or short circuit (80
o
C t)
2
Serial communication abnormality, faulty setting (determined by the water heat exchanger unit, remote control
side)
Faulty remote control reception[E01]
• Detection method: No communication addressed to the device has been received for 3 minutes
Remote control transmission fault [E02]
• Detection method: The device cannot read it’s own transmissions for 3 minutes
Faulty reception from the remote control by the water heat exchanger unit [E03]
• Detection method: There has been no communications addressed to the device for 3 minutes
Faulty reception from the outdoor side by the water heat exchanger unit [E04]
• Detection method There has been no communications addressed to the device for 3 minutes
Faulty transmission to the outdoor side from the water heat exchanger unit [E05]
• Detection method: The device cannot read it’s own transmissions for 3 minutes
Duplication of indoor unit address forbidden link cabling [E08]
• Detection method Another unit has the same indoor unit address as the unit
Faulty transmission by the water heat exchanger unit to the remote control [E13]
• Detection method: The device cannot read it’s own transmissions for 3 minutes
3
Faulty setting, setting not completed (determined by the water heat exchanger unit)
Faulty setting [L16]
• Detection method (setting temperature, chiller/water, shift) switch set outside specification range
Duplication of parallel address (when using RS485 communication) [L19]
• Detection method Another device has the same parallel address as the device
4
Other warnings (determined by the water heat exchanger unit)
Water heat exchanger unit freeze warning [P11]
• Detection method While the outdoor unit is operating, the freeze prevention temperature is detected by
either the freeze prevention sensor, the hot and cold water inlet/outlet sensor, or the refrigerant outlet
temperature sensor.
Interlock warning (ancillary equipment)[P23]
• Detection method Within 30 seconds after a hot and cold water pump operate command, the interlock
does not turn ON, or, the interlock turns off during a hot and cold water pump operate command.
Non-volatile memory (EEPROM) abnormality [F29]
• Detection method Inability to write normally
Summary of Contents for SGP-E120J2GU2
Page 49: ...Design D 5 2 Operating temperature ranges for heating and cooling Cooling Heating ...
Page 87: ...Design D 43 8 Salt resistant specification ...
Page 109: ...Construction E 22 4 Outdoor unit installation and construction ...
Page 110: ...Construction E 23 4 Outdoor unit installation and construction ...
Page 111: ...Construction E 24 4 Outdoor unit installation and construction ...
Page 112: ...Construction E 25 4 Outdoor unit installation and construction ...
Page 113: ...Construction E 26 4 Outdoor unit installation and construction ...
Page 114: ...Construction E 27 4 Outdoor unit installation and construction ...
Page 115: ...Construction E 28 4 Outdoor unit installation and construction ...
Page 116: ...Construction E 29 4 Outdoor unit installation and construction ...
Page 117: ...Construction E 30 4 Outdoor unit installation and construction ...
Page 118: ...Construction E 31 4 Outdoor unit installation and construction ...
Page 119: ...Construction E 32 4 Outdoor unit installation and construction ...
Page 120: ...Construction E 33 4 Outdoor unit installation and construction ...
Page 121: ...Construction E 34 4 Outdoor unit installation and construction ...
Page 122: ...Construction E 35 4 Outdoor unit installation and construction ...
Page 123: ...Construction E 36 4 Outdoor unit installation and construction ...
Page 124: ...Construction E 37 4 Outdoor unit installation and construction ...
Page 127: ...Construction E 40 5 Commissioning ...
Page 128: ...Construction E 41 5 Commissioning ...
Page 129: ...Construction E 42 5 Commissioning ...
Page 130: ...Construction E 43 5 Commissioning ...
Page 131: ...Construction E 44 5 Commissioning ...
Page 132: ...Construction E 45 5 Commissioning ...
Page 133: ...Construction E 46 5 Commissioning ...
Page 134: ...Construction E 47 5 Commissioning ...
Page 135: ...Construction E 48 5 Commissioning ...
Page 136: ...Construction E 49 5 Commissioning ...
Page 137: ...Construction E 50 5 Commissioning ...
Page 138: ...Construction E 51 5 Commissioning ...
Page 139: ...Construction E 52 5 Commissioning ...
Page 140: ...Construction E 53 5 Commissioning ...
Page 141: ...Construction E 54 5 Commissioning ...
Page 142: ...Construction E 55 5 Commissioning ...
Page 143: ...Separately Contents 1 Parts for the outdoor unit 1 Exhaust extension kit F 2 F 1 ...
Page 150: ...Periodicinspection G 3 1 Periodic maintenance contract 70 90 Type 120 150 190 Type ...
Page 155: ...Water heat exchange unit H 5 3 External view ...
Page 158: ...Water heat exchange unit H 8 4 Specification 2 External dimension diagram ...
Page 161: ...Water heat exchange unit H 11 4 Specification ...