Construction
E - 5
1. Points regarding refrigerant piping construction
(3) Refrigerant piping connection operations
1
Refrigerant piping materials
Piping should be “phosphorous de-oxidized copper seamless tube (C1220T).” Piping size shall be in accordance
with the following table.
●
All the unit piping, including the branch must be insulated. The gas side system (thick pipe) must be
insulated to greater than 120
o
C, and the liquid side (thin pipe) to greater than 80
o
C. (See Figure 1.)
For external diameters of 38.1mm or more the thickness should be
15mm, and for other sizes it should be 10mm.
If the conditions within the ceiling can exceed DB30
o
C or RH70%
then this thickness should be increased.
Improper insulationg can be the cause of water leaks and
condensation.
Use separate conduit for the electricity cables and the operation
cables. If the same conduit is used, a malfunction may result from
the effects of noise and induction.
Caution
Nominal external
diameter
φ
6.35
φ
9.52
φ
12.7
φ
15.88
φ
19.05
φ
22.2
φ
25.4
φ
28.58
φ
31.75
φ
38.1
φ
41.28
φ
44.45
φ
50.8
Thickness T0.8 T0.8 T0.8 T1.0 T1.0 T1.15 T1.0 T1.0 T1.1 T1.15 T1.2 T1.25 T1.4
Specification
O
material
1/2H or H material
2
Cautions regarding construction
Thermal insulation
(heat resistant to
greater than 120 )
Operation cable
Thermal insulation
Gas pipe side
(thick pipe)
Liquid pipe side
(thin pipe)
Ornamental tape
(to prevent rain
and water access)
3
Select the gas pipe (thick pipe), liquid pipe (thin pipe), branches (separately sold) and make necessary
preparations for installation.
●
After cutting the pipe, remove all burrs, and correctly finish the ends.
(similarly for separately sold branch fittings)
●
During cutting and bending operations do not damage the pipe.
●
Make sure that no water or sand can enter the pipe.
4
Connecting pipes
●
Carry out as follows.
1) Remove the fixing rubber by removing the gas pipe and the liquid pipe fixing
panel from the piping connection panel (See Fig. 3.).
2) Connect the piping, and braze.
3) Return the fixing rubber to the gas pipe and the liquid pipe. (Fig. 4)
Caution
Before brazing operations, complete the following.
●
The rubber for fixing the pipe is not resistant to heat, so before brazing be sure to remove it.
●
During brazing, cool the piping with wet cloth, etc. so that the heat does not cause damage to the valve
inside of the equipment.
●
Commercial anti-oxidants have adverse reactions on refrigerants and the refrigeration oil, so they should not
be used
Piping
connection
panel
Liquid pipe
fixing panel
Gas pipe
fixing rubber
Gas pipe
fixing panel
Liquid pipe
fixing rubber
Liquid pipe
(thin pipe)
Gas pipe
(thick pipe)
Brazing
Fig. 1
Fig. 2
Fig. 3
Fig. 4
Summary of Contents for SGP-E120J2GU2
Page 49: ...Design D 5 2 Operating temperature ranges for heating and cooling Cooling Heating ...
Page 87: ...Design D 43 8 Salt resistant specification ...
Page 109: ...Construction E 22 4 Outdoor unit installation and construction ...
Page 110: ...Construction E 23 4 Outdoor unit installation and construction ...
Page 111: ...Construction E 24 4 Outdoor unit installation and construction ...
Page 112: ...Construction E 25 4 Outdoor unit installation and construction ...
Page 113: ...Construction E 26 4 Outdoor unit installation and construction ...
Page 114: ...Construction E 27 4 Outdoor unit installation and construction ...
Page 115: ...Construction E 28 4 Outdoor unit installation and construction ...
Page 116: ...Construction E 29 4 Outdoor unit installation and construction ...
Page 117: ...Construction E 30 4 Outdoor unit installation and construction ...
Page 118: ...Construction E 31 4 Outdoor unit installation and construction ...
Page 119: ...Construction E 32 4 Outdoor unit installation and construction ...
Page 120: ...Construction E 33 4 Outdoor unit installation and construction ...
Page 121: ...Construction E 34 4 Outdoor unit installation and construction ...
Page 122: ...Construction E 35 4 Outdoor unit installation and construction ...
Page 123: ...Construction E 36 4 Outdoor unit installation and construction ...
Page 124: ...Construction E 37 4 Outdoor unit installation and construction ...
Page 127: ...Construction E 40 5 Commissioning ...
Page 128: ...Construction E 41 5 Commissioning ...
Page 129: ...Construction E 42 5 Commissioning ...
Page 130: ...Construction E 43 5 Commissioning ...
Page 131: ...Construction E 44 5 Commissioning ...
Page 132: ...Construction E 45 5 Commissioning ...
Page 133: ...Construction E 46 5 Commissioning ...
Page 134: ...Construction E 47 5 Commissioning ...
Page 135: ...Construction E 48 5 Commissioning ...
Page 136: ...Construction E 49 5 Commissioning ...
Page 137: ...Construction E 50 5 Commissioning ...
Page 138: ...Construction E 51 5 Commissioning ...
Page 139: ...Construction E 52 5 Commissioning ...
Page 140: ...Construction E 53 5 Commissioning ...
Page 141: ...Construction E 54 5 Commissioning ...
Page 142: ...Construction E 55 5 Commissioning ...
Page 143: ...Separately Contents 1 Parts for the outdoor unit 1 Exhaust extension kit F 2 F 1 ...
Page 150: ...Periodicinspection G 3 1 Periodic maintenance contract 70 90 Type 120 150 190 Type ...
Page 155: ...Water heat exchange unit H 5 3 External view ...
Page 158: ...Water heat exchange unit H 8 4 Specification 2 External dimension diagram ...
Page 161: ...Water heat exchange unit H 11 4 Specification ...