Design
D - 28
(1) Earthquake resistance calculations
For carrying out earthquake resistance calculations, there are various earthquake resistance ranks, as shown in the table
below. Gas heat pump air conditioning equipment should be dealt with as common use equipment.
•Earthquake resistant equipment ranks
Earthquake resistance ranks and their meaning are as follows
(2)Method of verifying the strength of foundation bolts during an earthquake
●
Calculation formulae and table of allowable stresses
•Design earthquake force
1)The design earthquake force consists of a horizontal force and a vertical force, acting simultaneously on the equipment
through the center of gravity.
2)The design earthquake force is given by the following formula.
Section through the short side
Equipment
(self weight W)
(pull out
force)
Foundation bolt
Notes
1) “Earthquake resistant” applies to important building services
2) “Common use applies to normal building services
3) Equipment with earthquake resistant supports is equipment
provided with earthquake resistant stoppers to prevent
amplification of shaking due to resonance. In this case, a
shock absorbing material is placed between the stopper and
the equipment so that the earthquake resistant stoppers are
not damaged or deformed by impact.
Notes
1) Small scale repairs are repairs that take up to 2 days
2) Main frame strength (static), fasteners for each component (bolts etc.).
3) Indicates foundation bolt calculation etc.
*From”Earthquake resistant equipment specification criteria for package air conditioners and water chillers”,
published by the Japan Refrigeration and Air Conditioning Industry Association.
The above criteria are applicable to normal air conditioning equipment installed in buildings subject to normal
approval procedures under the Buildings Standard Law (i.e., less than 60m high)
F
v
= F
H
2
1
F
H
=K
H
W
.
F
H
:Design horizontal force (N) W : Equipment operating weight(N)
K
H
: Design horizontal magnitude
F
V
: Design vertical force (N)
7. Center of gravity position and earthquake resistant design
Summary of Contents for SGP-E120J2GU2
Page 49: ...Design D 5 2 Operating temperature ranges for heating and cooling Cooling Heating ...
Page 87: ...Design D 43 8 Salt resistant specification ...
Page 109: ...Construction E 22 4 Outdoor unit installation and construction ...
Page 110: ...Construction E 23 4 Outdoor unit installation and construction ...
Page 111: ...Construction E 24 4 Outdoor unit installation and construction ...
Page 112: ...Construction E 25 4 Outdoor unit installation and construction ...
Page 113: ...Construction E 26 4 Outdoor unit installation and construction ...
Page 114: ...Construction E 27 4 Outdoor unit installation and construction ...
Page 115: ...Construction E 28 4 Outdoor unit installation and construction ...
Page 116: ...Construction E 29 4 Outdoor unit installation and construction ...
Page 117: ...Construction E 30 4 Outdoor unit installation and construction ...
Page 118: ...Construction E 31 4 Outdoor unit installation and construction ...
Page 119: ...Construction E 32 4 Outdoor unit installation and construction ...
Page 120: ...Construction E 33 4 Outdoor unit installation and construction ...
Page 121: ...Construction E 34 4 Outdoor unit installation and construction ...
Page 122: ...Construction E 35 4 Outdoor unit installation and construction ...
Page 123: ...Construction E 36 4 Outdoor unit installation and construction ...
Page 124: ...Construction E 37 4 Outdoor unit installation and construction ...
Page 127: ...Construction E 40 5 Commissioning ...
Page 128: ...Construction E 41 5 Commissioning ...
Page 129: ...Construction E 42 5 Commissioning ...
Page 130: ...Construction E 43 5 Commissioning ...
Page 131: ...Construction E 44 5 Commissioning ...
Page 132: ...Construction E 45 5 Commissioning ...
Page 133: ...Construction E 46 5 Commissioning ...
Page 134: ...Construction E 47 5 Commissioning ...
Page 135: ...Construction E 48 5 Commissioning ...
Page 136: ...Construction E 49 5 Commissioning ...
Page 137: ...Construction E 50 5 Commissioning ...
Page 138: ...Construction E 51 5 Commissioning ...
Page 139: ...Construction E 52 5 Commissioning ...
Page 140: ...Construction E 53 5 Commissioning ...
Page 141: ...Construction E 54 5 Commissioning ...
Page 142: ...Construction E 55 5 Commissioning ...
Page 143: ...Separately Contents 1 Parts for the outdoor unit 1 Exhaust extension kit F 2 F 1 ...
Page 150: ...Periodicinspection G 3 1 Periodic maintenance contract 70 90 Type 120 150 190 Type ...
Page 155: ...Water heat exchange unit H 5 3 External view ...
Page 158: ...Water heat exchange unit H 8 4 Specification 2 External dimension diagram ...
Page 161: ...Water heat exchange unit H 11 4 Specification ...