Design
D - 15
(1) Combined installation criteria
If several outdoor units are installed on the roof of a building, for example, the air path for a normal maintenance
space is insufficient, as exhaust air from the outdoor unit can be again sucked into the outdoor unit, to create a kind
of short circuit.
Because of this the surrounding air temperature can rise, and the cooling capacity can reduce significantly, or an
emergency stop may occur.
When making a collective installation with GHP, in order to ensure a sufficient air path the following installation
criteria must be followed. Also, compared with cooling, the effect on heating is small, so if the cooling criteria for
installation are followed there should be no problem.
*For unusual installation circumstances, consider these criteria appropriately before making decisions.
1
Scope of applicability of criteria
These criteria are applicable to installations satisfying either of the following two situations.
• When there are eight or more outdoor units in a combined installation
• In installations with seven or fewer outdoor units but in the surroundings there are walls that might prevent
the circulation of air.
2
Conditions for a combined installation
In order to secure the necessary air flow, the following two conditions must both be satisfied in a combined
installation.
• The space between outdoor units and rows of outdoor units must be well maintained.
• The area of flow of air from the surroundings to the combined outdoor units must be well maintained.
3
Parameters of a combined installation
Rows of outdoor units
La: average distance between outdoor units (m)
• When the distance between outdoor units is not equal, the distance La is the average.
• Position only up to 3 outdoor units near each other. For more than 3 units leave a prescribed distance every 3 units.
• If there are 6 or more units in a row, leave a gap of 1m every 3 units.
Lu: distance between rows (m)
• All Lu are to be equal.
L
N
: Row length (m)
L
M
: External dimension of the installation (m)
L
W
: Distance between the wall and the closest outdoor unit (m)
• When there is no wall L
W
= 6.
U
W
: Width of outdoor unit (m)
U
D
:
Depth of outdoor unit (m)
5. Criteria for positioning the outdoor unit
Summary of Contents for SGP-E120J2GU2
Page 49: ...Design D 5 2 Operating temperature ranges for heating and cooling Cooling Heating ...
Page 87: ...Design D 43 8 Salt resistant specification ...
Page 109: ...Construction E 22 4 Outdoor unit installation and construction ...
Page 110: ...Construction E 23 4 Outdoor unit installation and construction ...
Page 111: ...Construction E 24 4 Outdoor unit installation and construction ...
Page 112: ...Construction E 25 4 Outdoor unit installation and construction ...
Page 113: ...Construction E 26 4 Outdoor unit installation and construction ...
Page 114: ...Construction E 27 4 Outdoor unit installation and construction ...
Page 115: ...Construction E 28 4 Outdoor unit installation and construction ...
Page 116: ...Construction E 29 4 Outdoor unit installation and construction ...
Page 117: ...Construction E 30 4 Outdoor unit installation and construction ...
Page 118: ...Construction E 31 4 Outdoor unit installation and construction ...
Page 119: ...Construction E 32 4 Outdoor unit installation and construction ...
Page 120: ...Construction E 33 4 Outdoor unit installation and construction ...
Page 121: ...Construction E 34 4 Outdoor unit installation and construction ...
Page 122: ...Construction E 35 4 Outdoor unit installation and construction ...
Page 123: ...Construction E 36 4 Outdoor unit installation and construction ...
Page 124: ...Construction E 37 4 Outdoor unit installation and construction ...
Page 127: ...Construction E 40 5 Commissioning ...
Page 128: ...Construction E 41 5 Commissioning ...
Page 129: ...Construction E 42 5 Commissioning ...
Page 130: ...Construction E 43 5 Commissioning ...
Page 131: ...Construction E 44 5 Commissioning ...
Page 132: ...Construction E 45 5 Commissioning ...
Page 133: ...Construction E 46 5 Commissioning ...
Page 134: ...Construction E 47 5 Commissioning ...
Page 135: ...Construction E 48 5 Commissioning ...
Page 136: ...Construction E 49 5 Commissioning ...
Page 137: ...Construction E 50 5 Commissioning ...
Page 138: ...Construction E 51 5 Commissioning ...
Page 139: ...Construction E 52 5 Commissioning ...
Page 140: ...Construction E 53 5 Commissioning ...
Page 141: ...Construction E 54 5 Commissioning ...
Page 142: ...Construction E 55 5 Commissioning ...
Page 143: ...Separately Contents 1 Parts for the outdoor unit 1 Exhaust extension kit F 2 F 1 ...
Page 150: ...Periodicinspection G 3 1 Periodic maintenance contract 70 90 Type 120 150 190 Type ...
Page 155: ...Water heat exchange unit H 5 3 External view ...
Page 158: ...Water heat exchange unit H 8 4 Specification 2 External dimension diagram ...
Page 161: ...Water heat exchange unit H 11 4 Specification ...